Post Date: 27 Apr, 2017
Status: Approved
CEN Standards EN 15251:2007 and EN 16798-3:2017 may be used in lieu of ASHRAE 62.1-2013 for Feature 15, Part 1.
The project must meet Category I or II (described in Table 1) and must calculate the ventilation rate based on either of the below calculation methods, referenced in EN 15251: 2007, section B.1.3 ""Method based on ventilation rate per person or per m² floor area:""
1) the addition of the occupant and building values (see section B.1.2).
2) the highest value (maximum of the calculated value based on per person and the value based on per m² floor area from Table B.3).
Additionally, the requirements of CEN Standard EN 15251-2007 must be met and the performance requirements of CEN Standard EN 16798-3:2017 related to ventilation and room conditioning systems must be met (excluding section 7.3, Thermal Environment; section 7.6, Acoustic Environment; section A.16; and section A.17).