Post Date: 29 May, 2018
Status: Approved
Where projects are restricted from implementing a demand-controlled ventilation system or are unable to retrofit the existing ventilation system to be demand-controlled, the requirements of Feature 03 Part 2 may be met through the following conditions for outdoor air supply rate, whichever is more stringent:
1. Exceed the ventilation rates set in ASHRAE 62.1-2013 (Ventilation Rate Procedure or IAQ Procedure) by 40%. Note that if this feature part applies to more than 50% of the total floor area at the project site, projects are not eligible to receive points for Feature 15 Part 1a.
2. Provide a ventilation supply rate of 12 L/s (25 CFM) per person or higher.